Dixell Xw60ls Manual Apr 2026

| i1P | Function | |-------|-----------| | oP | Door switch – normal open | | cL | Door switch – normal closed | | EAL | External alarm (generic) | | bAL | Serious alarm (compressor stop) | | PAL | Pressure switch alarm | | dor | Door switch with fan cut-off and defrost inhibition |

For : | Parameter | Value | |-----------|-------| | Set | -18°C | | Hy | 2°C | | LS | -30°C | | US | -10°C | | dtE | 15°C | | MdF | 30 minutes | | idF | 8 hours | Conclusion The Dixell XW60LS is a reliable, flexible controller for commercial refrigeration. Mastering its parameter structure, wiring, and alarm handling allows technicians to optimize energy efficiency, protect compressors, and maintain precise temperature control. Always keep a copy of the official parameter list and use the Hot Key for rapid deployment across multiple units. dixell xw60ls manual

| Parameter | Value | |-----------|-------| | Set | 2°C | | Hy | 4°C (cut-in at 4°C, cut-out at 2°C) | | LS | -5°C | | US | 8°C | | tyP | 0 (electric) | | dtE | 8°C | | idF | 6 hours | | MdF | 20 minutes | | Fnc | 2 (fan with compressor, off during defrost) | | AC | 5 min | | i1P | Function | |-------|-----------| | oP

If configured as dor (door switch): opening the door stops fans and displays dA after a delay (parameter doA ). Closing the door restarts normal operation. The XW60LS flashes an alarm code on the display while the red LED blinks. | Parameter | Value | |-----------|-------| | Set